Domestic Air Source Heat Pump
-
Price:
Negotiable
- minimum:
- Total supply:
-
Delivery term:
The date of payment from buyers deliver within days
-
seat:
Guangdong
-
Validity to:
Long-term effective
-
Last update:
2017-10-29 11:34
-
Browse the number:
289
Company Profile
Dongguan Golden Refrigeration Equipment Co., Ltd.By certification [File Integrity]
Contact:Ms. Aysha Wan(Mr.)
Email:
Telephone:
Phone:
Area:Guangdong
Address:Guangdong
Website: http://dghaoli.liyangyacht.com/
Product Details
Domestic Air Source Heat Pump
Product Function
Widely used in building air conditioning system, small and medium-sized office,
workshop, restaurants, villas and other air conditioning environment.
Product Advantage
1. Rated Cooling Capacity Based on: Chilled water inlet/outlet temp. 12°C/7°C,
Cooling water inlet/outlet temp. 30°C/35°C,
2. Chilled Water Range: 5~20°C;
3. Cooling Water Range: 20~40°C;
4. Refrigerant: R22 / R407C / R410A / R134A is optional.
5. Designed with quality compressor(Danfoss, Copeland Brand etc) and multi-refrigeration circuits.
6. Compressors: 1~3 compressors design to save energy and power.
7. Well-structured safety protection and trouble indication system.
8. Brand of Compressor: Standard unit is Danfoss, Copeland, can guarantee reliable running, high efficiency, low noise & power saving and long use life.
You could choose other brands just like Bitzer, Dakin etc.
10. Electrostatic plastic sprayed outter casing, the outer panel is easy dismantlement to guarantee convenient usage and maintenance.
11. Microcomputer intelligent temperature controller, high precision digital display.
Product Parameter
Golden Item NO. HLLH~ | 08BM | 16BM | 20BM | 08AM | 16AM | 20AM | 33AM | 40AM | 33M | 40M | 44M | 57M | 76M |
Suitable area: | Southeast Asia, main Weat Asia, Middle East, Africa, main South America, South Austrilia …etc with winter temperature above -5DegC | ||||||||||||
Metel cabinet | Galvanized steel/Plastic coating | ||||||||||||
Compressor / Refrigerant | Scroll Copeland compressor / R410A | ||||||||||||
Power supply | 220/1/50 | 380/3/50 | 220/1/50 | 380/3/50 | |||||||||
Heat exchanger | High efficiency tube in tube heat exchanger | ||||||||||||
Expansion valve device | Emerson thermal expansion valve | ||||||||||||
Heating capacity (kW) | 8.1 | 16.4 | 19.5 | 8.1 | 16.4 | 19.5 | 32.8 | 39.1 | 32.8 | 39.1 | 43.4 | 57.2 | 75.6 |
Input power (kW) | 2.03 | 4.09 | 4.9 | 2.03 | 4.09 | 4.9 | 8.24 | 9.84 | 8.24 | 9.84 | 10.6 | 14.2 | 18.8 |
COP (Coefficient of Performance) | 3.99 | 4.01 | 3.98 | 3.99 | 4.01 | 3.98 | 3.98 | 3.97 | 3.98 | 3.97 | 4.09 | 4.03 | 4.02 |
Rated current (A) | 10.2 | 7.5 | 8.5 | 10.2 | 7.5 | 8.5 | 14.5 | 17 | 14.5 | 17 | 20 | 26 | 33 |
Rated water outlet temperature (ºC) | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 | 40 |
Max water outlet temperature(ºC) | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 | 45 |
Rated water producing volume (L/H) | 200 | 400 | 460 | 200 | 400 | 460 | 800 | 920 | 800 | 920 | 1050 | 1380 | 18500 |
Cooling capacity (kW) | 6.3 | 12.8 | 15.1 | 6.3 | 12.8 | 15.1 | 25.6 | 29.6 | 25.6 | 29.6 | 33.4 | 43.6 | 60.5 |
Input power (kW) | 2.32 | 4.71 | 5.42 | 2.32 | 4.71 | 5.42 | 9.42 | 10.6 | 9.42 | 10.6 | 12.3 | 15.9 | 22.3 |
EER | 2.72 | 2.72 | 2.79 | 2.72 | 2.72 | 2.79 | 2.72 | 2.79 | 2.72 | 2.79 | 2.72 | 2.74 | 2.71 |
Rated current (A) | 10.7 | 8 | 9.3 | 10.7 | 8 | 9.3 | 16 | 18.5 | 16 | 18.5 | 22 | 28 | 36 |
Rated water outlet temperature (ºC) | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 |
Max water outlet temperature(ºC) | 7 | 7 | 7 | 7 | 7 | 7 | 7 | 7 | 7 | 7 | 7 | 7 | 7 |
Rated water producing volume (L/H) | 1500 | 2800 | 3400 | 1500 | 2800 | 3400 | 5600 | 6700 | 5600 | 6700 | 7500 | 10200 | 13500 |
Water connection size | DN25 | DN25 | DN25 | DN25 | DN25 | DN25 | DN32 | DN32 | DN32 | DN32 | DN50 | DN50 | DN65 |
Working temperature range (ºC) | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 |
IP Grade (Level of protection) | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 |
Anti-electric shock Rate | I | I | I | I | I | I | I | I | I | I | I | I | I |
Noise at 1m (dB(A)) | ≤55 | ≤58 | ≤58 | ≤58 | ≤60 | ≤60 | ≤65 | ≤65 | ≤65 | ≤65 | ≤68 | ≤68 | ≤70 |
Net weight(kg) | 100 | 145 | 155 | 100 | 145 | 155 | 300 | 330 | 300 | 330 | 372 | 482 | 582 |
Gross weight(kg) | 106 | 155 | 165 | 106 | 155 | 165 | 320 | 350 | 320 | 350 | 412 | 532 | 643 |
Delivery & Payment
1. Packing: Standard Plywood Package.
2. Delivery Day: 25 days after deposit is confirmed.
3. Delivery term: CIF,FOB or CNF EX-Work are welcomed.
4. Payment term: T/T, 30% deposit, 70% before delivery; Or 100% Irrevocable non-transferred L/C at sight.
5. Warranty: Warranty for 12 months from the date of shipment from the factory, whichever comes first.
6. Validity: 20 days.
7. Payment currency: USD or EX-Work CNY.
FAQ
Q: What information do you need to provide in order to get a quotation?
A: Generally, for industrial water chiller we need to know the following information in order to suggest the suitable water chiller models and for providing the quotation.
1) Air cooled or water cooled?
2) Cooling Capacity / Heating Capacity.
3) Power Supply.
4) Refrigerant.
5) Chilled water outlet temperature / Hot water temperature
6) Order Quantity etc.
Q: Can I have a samples for testing before ordering products?
A: Yes, you can.
We sincerely suggest that customers should have some samples of required fans for testing because the truly performance of fans can be fully demonstrated after testing is conducted.
Q: What is the warranty of products?
A: For 1 year warranty. Free to amend and change the parts due to quality reasons in warranty year.